← Back

Modicon M221 Firmware

modicon_m221_firmware

Vendor: Schneider Electric • 16 CVEs

CVEs (16)

CVE
VENDORS
PRODUCTS
UPDATED
PUBLISHED
CVSS
1Schneider Electric
1Modicon M221 Firmware
Jun 17, 2026
Dec 11, 2020
N/A· v4
5.5 MEDIUM· v3
2.1 LOW· v2
A CWE-760: Use of a One-Way Hash with a Predictable Salt vulnerability exists in Modicon M221 (all references, all versions), that could allow an attacker to pre-compute the hash value using dictionary attack technique s...Show more
A CWE-760: Use of a One-Way Hash with a Predictable Salt vulnerability exists in Modicon M221 (all references, all versions), that could allow an attacker to pre-compute the hash value using dictionary attack technique such as rainbow tables, effectively disabling the protection that an unpredictable salt would provide.Show less
1Schneider Electric
1Modicon M221 Firmware
Jun 17, 2026
Nov 19, 2020
N/A· v4
4.3 MEDIUM· v3
3.3 LOW· v2
A CWE-200: Exposure of Sensitive Information to an Unauthorized Actor vulnerability exists in Modicon M221 (all references, all versions) that could allow non sensitive information disclosure when the attacker has captur...Show more
A CWE-200: Exposure of Sensitive Information to an Unauthorized Actor vulnerability exists in Modicon M221 (all references, all versions) that could allow non sensitive information disclosure when the attacker has captured the traffic between EcoStruxure Machine - Basic software and Modicon M221 controller.Show less
1Schneider Electric
1Modicon M221 Firmware
Jun 17, 2026
Nov 19, 2020
N/A· v4
5.7 MEDIUM· v3
2.9 LOW· v2
A CWE-311: Missing Encryption of Sensitive Data vulnerability exists in Modicon M221 (all references, all versions) that could allow the attacker to find the password hash when the attacker has captured the traffic betwe...Show more
A CWE-311: Missing Encryption of Sensitive Data vulnerability exists in Modicon M221 (all references, all versions) that could allow the attacker to find the password hash when the attacker has captured the traffic between EcoStruxure Machine - Basic software and Modicon M221 controller and broke the encryption keys.Show less
1Schneider Electric
1Modicon M221 Firmware
Jun 17, 2026
Nov 19, 2020
N/A· v4
7.3 HIGH· v3
4.3 MEDIUM· v2
A CWE-334: Small Space of Random Values vulnerability exists in Modicon M221 (all references, all versions) that could allow the attacker to break the encryption keys when the attacker has captured the traffic between Ec...Show more
A CWE-334: Small Space of Random Values vulnerability exists in Modicon M221 (all references, all versions) that could allow the attacker to break the encryption keys when the attacker has captured the traffic between EcoStruxure Machine - Basic software and Modicon M221 controller.Show less
1Schneider Electric
1Modicon M221 Firmware
Jun 17, 2026
Nov 19, 2020
N/A· v4
7.3 HIGH· v3
4.3 MEDIUM· v2
A CWE-326: Inadequate Encryption Strength vulnerability exists in Modicon M221 (all references, all versions) that could allow the attacker to break the encryption key when the attacker has captured the traffic between E...Show more
A CWE-326: Inadequate Encryption Strength vulnerability exists in Modicon M221 (all references, all versions) that could allow the attacker to break the encryption key when the attacker has captured the traffic between EcoStruxure Machine - Basic software and Modicon M221 controller.Show less
1Schneider Electric
5Ecostruxure Machine Expert
Modicon M100 FirmwareModicon M200 Firmware+2 more
Jun 17, 2026
Apr 22, 2020
N/A· v4
9.8 CRITICAL· v3
7.5 HIGH· v2
A CWE-74: Improper Neutralization of Special Elements in Output Used by a Downstream Component ('Injection') vulnerability exists on EcoStruxure Machine Expert – Basic or SoMachine Basic programming software (versions in...Show more
A CWE-74: Improper Neutralization of Special Elements in Output Used by a Downstream Component ('Injection') vulnerability exists on EcoStruxure Machine Expert – Basic or SoMachine Basic programming software (versions in security notification). The result of this vulnerability, DLL substitution, could allow the transference of malicious code to the controller.Show less
1Schneider Electric
12Atv Imc Drive Controller Firmware
Modicon Lmc058 FirmwareModicon Lmc078 Firmware+9 more
Jun 17, 2026
May 22, 2019
N/A· v4
8.2 HIGH· v3
6.4 MEDIUM· v2
A CWE-306: Missing Authentication for Critical Function vulnerability exists which could cause a modification of device IP configuration (IP address, network mask and gateway IP address) when a specific Ethernet frame is...Show more
A CWE-306: Missing Authentication for Critical Function vulnerability exists which could cause a modification of device IP configuration (IP address, network mask and gateway IP address) when a specific Ethernet frame is received in all versions of: Modicon M100, Modicon M200, Modicon M221, ATV IMC drive controller, Modicon M241, Modicon M251, Modicon M258, Modicon LMC058, Modicon LMC078, PacDrive Eco ,PacDrive Pro, PacDrive Pro2Show less
1Schneider Electric
2Modicon M221 Firmware
Somachine Basic
Jun 17, 2026
May 22, 2019
N/A· v4
5.3 MEDIUM· v3
5.0 MEDIUM· v2
A Environment (CWE-2) vulnerability exists in SoMachine Basic, all versions, and Modicon M221(all references, all versions prior to firmware V1.10.0.0) which could cause remote launch of SoMachine Basic when sending craf...Show more
A Environment (CWE-2) vulnerability exists in SoMachine Basic, all versions, and Modicon M221(all references, all versions prior to firmware V1.10.0.0) which could cause remote launch of SoMachine Basic when sending crafted ethernet message.Show less
1Schneider Electric
2Modicon M221 Firmware
Somachine Basic
Jun 17, 2026
May 22, 2019
N/A· v4
5.5 MEDIUM· v3
2.1 LOW· v2
An Incorrect Default Permissions (CWE-276) vulnerability exists in SoMachine Basic, all versions, and Modicon M221(all references, all versions prior to firmware V1.10.0.0) which could cause unauthorized access to SoMach...Show more
An Incorrect Default Permissions (CWE-276) vulnerability exists in SoMachine Basic, all versions, and Modicon M221(all references, all versions prior to firmware V1.10.0.0) which could cause unauthorized access to SoMachine Basic resource files when logged on the system hosting SoMachine Basic.Show less
1Schneider Electric
2Modicon M221 Firmware
Somachine Basic
Jun 17, 2026
May 22, 2019
N/A· v4
7.5 HIGH· v3
5.0 MEDIUM· v2
An Environment (CWE-2) vulnerability exists in SoMachine Basic, all versions, and Modicon M221(all references, all versions prior to firmware V1.10.0.0) which could cause cycle time impact when flooding the M221 ethernet...Show more
An Environment (CWE-2) vulnerability exists in SoMachine Basic, all versions, and Modicon M221(all references, all versions prior to firmware V1.10.0.0) which could cause cycle time impact when flooding the M221 ethernet interface while the Ethernet/IP adapter is activated.Show less
5Abb
PhoenixcontactSchneider Electric+2 more
106ed1052 1cc01 0ba8 Firmware
6es7211 1ae40 0xb0 Firmware6es7314 6eh04 0ab0 Firmware+7 more
Jun 17, 2026
Apr 17, 2019
N/A· v4
7.5 HIGH· v3
5.0 MEDIUM· v2
ABB, Phoenix Contact, Schneider Electric, Siemens, WAGO - Programmable Logic Controllers, multiple versions. Researchers have found some controllers are susceptible to a denial-of-service attack due to a flood of network...Show more
ABB, Phoenix Contact, Schneider Electric, Siemens, WAGO - Programmable Logic Controllers, multiple versions. Researchers have found some controllers are susceptible to a denial-of-service attack due to a flood of network packets.Show less
1Schneider Electric
1Modicon M221 Firmware
Jun 17, 2026
Aug 29, 2018
N/A· v4
7.5 HIGH· v3
5.0 MEDIUM· v2
A Permissions, Privileges, and Access Control vulnerability exists in Schneider Electric's Modicon M221 product (all references, all versions prior to firmware V1.6.2.0). The vulnerability allows unauthorized users to de...Show more
A Permissions, Privileges, and Access Control vulnerability exists in Schneider Electric's Modicon M221 product (all references, all versions prior to firmware V1.6.2.0). The vulnerability allows unauthorized users to decode the password using rainbow table.Show less
1Schneider Electric
1Modicon M221 Firmware
Jun 17, 2026
Aug 29, 2018
N/A· v4
9.8 CRITICAL· v3
7.5 HIGH· v2
A Permissions, Privileges, and Access Control vulnerability exists in Schneider Electric's Modicon M221 product (all references, all versions prior to firmware V1.6.2.0). The vulnerability allows unauthorized users to ov...Show more
A Permissions, Privileges, and Access Control vulnerability exists in Schneider Electric's Modicon M221 product (all references, all versions prior to firmware V1.6.2.0). The vulnerability allows unauthorized users to overwrite the original password with their password. If an attacker exploits this vulnerability and overwrite the password, the attacker can upload the original program from the PLC.Show less
1Schneider Electric
1Modicon M221 Firmware
Jun 17, 2026
Aug 29, 2018
N/A· v4
9.8 CRITICAL· v3
7.5 HIGH· v2
An Information Management Error vulnerability exists in Schneider Electric's Modicon M221 product (all references, all versions prior to firmware V1.6.2.0). The vulnerability allows unauthorized users to replay authentic...Show more
An Information Management Error vulnerability exists in Schneider Electric's Modicon M221 product (all references, all versions prior to firmware V1.6.2.0). The vulnerability allows unauthorized users to replay authentication sequences. If an attacker exploits this vulnerability and connects to a Modicon M221, the attacker can upload the original program from the PLC.Show less
1Schneider Electric
1Modicon M221 Firmware
Jun 17, 2026
Aug 29, 2018
N/A· v4
7.5 HIGH· v3
7.8 HIGH· v2
An Improper Check for Unusual or Exceptional Conditions vulnerability exists in Schneider Electric's Modicon M221 product (all references, all versions prior to firmware V1.6.2.0). The vulnerability allows unauthorized u...Show more
An Improper Check for Unusual or Exceptional Conditions vulnerability exists in Schneider Electric's Modicon M221 product (all references, all versions prior to firmware V1.6.2.0). The vulnerability allows unauthorized users to remotely reboot Modicon M221 using crafted programing protocol frames.Show less
1Schneider Electric
3Modicon M221 Firmware
Modicon M241 FirmwareModicon M251 Firmware
Jun 4, 2026
Jun 30, 2017
N/A· v4
6.5 MEDIUM· v3
6.4 MEDIUM· v2
A predictable value range from previous values issue was discovered in Schneider Electric Modicon PLCs Modicon M221, firmware versions prior to Version 1.5.0.0, Modicon M241, firmware versions prior to Version 4.0.5.11,...Show more
A predictable value range from previous values issue was discovered in Schneider Electric Modicon PLCs Modicon M221, firmware versions prior to Version 1.5.0.0, Modicon M241, firmware versions prior to Version 4.0.5.11, and Modicon M251, firmware versions prior to Version 4.0.5.11. The affected products generate insufficiently random TCP initial sequence numbers that may allow an attacker to predict the numbers from previous values. This may allow an attacker to spoof or disrupt TCP connections.Show less