← Back

Automationdirect

automationdirect

35 CVEs • 139 products

Products (139)

Click to collapse
Toggle
Click Plc
click_plc
C More Plc
c-more_plc
C More Micro
c-more_micro
Gs Drives
gs_drives
Ea9 Pgmsw
ea9-pgmsw
Ea9 Rhmi
ea9-rhmi
Ea9 T10cl
ea9-t10cl
Ea9 T10wcl
ea9-t10wcl
Ea9 T12cl
ea9-t12cl
Ea9 T15cl
ea9-t15cl
Ea9 T15cl R
ea9-t15cl-r
Ea9 T6cl
ea9-t6cl
Ea9 T6cl R
ea9-t6cl-r
Ea9 T7cl
ea9-t7cl
Ea9 T7cl R
ea9-t7cl-r
Ea9 T8cl
ea9-t8cl
C0 10dd1e D
c0-10dd1e-d
C0 10dd2e D
c0-10dd2e-d
C0 10dre D
c0-10dre-d
C0 10are D
c0-10are-d
C0 11dd1e D
c0-11dd1e-d
C0 11dd2e D
c0-11dd2e-d
C0 11dre D
c0-11dre-d
C0 11are D
c0-11are-d

CVEs (35)

CVE
VENDORS
PRODUCTS
UPDATED
PUBLISHED
CVSS
1Automationdirect
12C More Ea9 Pgmsw Firmware
C More Ea9 Rhmi FirmwareC More Ea9 T10cl Firmware+9 more
Jun 17, 2026
Aug 31, 2022
N/A· v4
7.5 HIGH· v3
N/A· v2
AutomationDirect C-more EA9 HTTP webserver uses an insecure mechanism to transport credentials from client to web server, which may allow an attacker to obtain the login credentials and login as a valid user. This issue...Show more
AutomationDirect C-more EA9 HTTP webserver uses an insecure mechanism to transport credentials from client to web server, which may allow an attacker to obtain the login credentials and login as a valid user. This issue affects: AutomationDirect C-more EA9 EA9-T6CL versions prior to 6.73; EA9-T6CL-R versions prior to 6.73; EA9-T7CL versions prior to 6.73; EA9-T7CL-R versions prior to 6.73; EA9-T8CL versions prior to 6.73; EA9-T10CL versions prior to 6.73; EA9-T10WCL versions prior to 6.73; EA9-T12CL versions prior to 6.73; EA9-T15CL versions prior to 6.73; EA9-RHMI versions prior to 6.73; EA9-PGMSW versions prior to 6.73;Show less
1Automationdirect
9D0 06aa Firmware
D0 06ar FirmwareD0 06da Firmware+6 more
Jun 17, 2026
Aug 31, 2022
N/A· v4
7.5 HIGH· v3
N/A· v2
AutomationDirect DirectLOGIC is vulnerable to a a specially crafted packet can be sent continuously to the PLC to prevent access from DirectSoft and other devices, causing a denial-of-service condition. This issue affect...Show more
AutomationDirect DirectLOGIC is vulnerable to a a specially crafted packet can be sent continuously to the PLC to prevent access from DirectSoft and other devices, causing a denial-of-service condition. This issue affects: AutomationDirect DirectLOGIC D0-06 series CPUs D0-06DD1 versions prior to 2.72; D0-06DD2 versions prior to 2.72; D0-06DR versions prior to 2.72; D0-06DA versions prior to 2.72; D0-06AR versions prior to 2.72; D0-06AA versions prior to 2.72; D0-06DD1-D versions prior to 2.72; D0-06DD2-D versions prior to 2.72; D0-06DR-D versions prior to 2.72;Show less
1Automationdirect
9D0 06aa Firmware
D0 06ar FirmwareD0 06da Firmware+6 more
Jun 17, 2026
Aug 31, 2022
N/A· v4
9.1 CRITICAL· v3
N/A· v2
AutomationDirect DirectLOGIC is vulnerable to a specifically crafted serial message to the CPU serial port that will cause the PLC to respond with the PLC password in cleartext. This could allow an attacker to access and...Show more
AutomationDirect DirectLOGIC is vulnerable to a specifically crafted serial message to the CPU serial port that will cause the PLC to respond with the PLC password in cleartext. This could allow an attacker to access and make unauthorized changes. This issue affects: AutomationDirect DirectLOGIC D0-06 series CPUs D0-06DD1 versions prior to 2.72; D0-06DD2 versions prior to 2.72; D0-06DR versions prior to 2.72; D0-06DA versions prior to 2.72; D0-06AR versions prior to 2.72; D0-06AA versions prior to 2.72; D0-06DD1-D versions prior to 2.72; D0-06DD2-D versions prior to 2.72; D0-06DR-D versions prior to 2.72;Show less
1Automationdirect
20C0 10are D Firmware
C0 10dd1e D FirmwareC0 10dd2e D Firmware+17 more
Jun 17, 2026
Apr 4, 2022
N/A· v4
9.8 CRITICAL· v3
7.5 HIGH· v2
After Automation Direct CLICK PLC CPU Modules: C0-1x CPUs with firmware prior to v3.00 is unlocked by an authorized user, the unlocked state does not timeout. If the programming software is interrupted, the PLC remains u...Show more
After Automation Direct CLICK PLC CPU Modules: C0-1x CPUs with firmware prior to v3.00 is unlocked by an authorized user, the unlocked state does not timeout. If the programming software is interrupted, the PLC remains unlocked. All subsequent programming connections are allowed without authorization. The PLC is only relocked by a power cycle, or when the programming software disconnects correctly.Show less
1Automationdirect
20C0 10are D Firmware
C0 10dd1e D FirmwareC0 10dd2e D Firmware+17 more
Jun 17, 2026
Apr 4, 2022
N/A· v4
9.8 CRITICAL· v3
7.5 HIGH· v2
All programming connections receive the same unlocked privileges, which can result in a privilege escalation. During the time Automation Direct CLICK PLC CPU Modules: C0-1x CPUs with firmware prior to v3.00 is unlocked b...Show more
All programming connections receive the same unlocked privileges, which can result in a privilege escalation. During the time Automation Direct CLICK PLC CPU Modules: C0-1x CPUs with firmware prior to v3.00 is unlocked by an authorized user, an attacker can connect to the PLC and read the project without authorization.Show less
1Automationdirect
20C0 10are D Firmware
C0 10dd1e D FirmwareC0 10dd2e D Firmware+17 more
Jun 17, 2026
Apr 4, 2022
N/A· v4
7.5 HIGH· v3
5.0 MEDIUM· v2
Automation Direct CLICK PLC CPU Modules: C0-1x CPUs with firmware prior to v3.00 passwords are sent as plaintext during unlocking and project transfers. An attacker who has network visibility can observe the password exc...Show more
Automation Direct CLICK PLC CPU Modules: C0-1x CPUs with firmware prior to v3.00 passwords are sent as plaintext during unlocking and project transfers. An attacker who has network visibility can observe the password exchange.Show less
1Automationdirect
20C0 10are D Firmware
C0 10dd1e D FirmwareC0 10dd2e D Firmware+17 more
Jun 17, 2026
Apr 4, 2022
N/A· v4
9.8 CRITICAL· v3
7.5 HIGH· v2
Automation Direct CLICK PLC CPU Modules: C0-1x CPUs with firmware prior to v3.00 does not protect against additional software programming connections. An attacker can connect to the PLC while an existing connection is al...Show more
Automation Direct CLICK PLC CPU Modules: C0-1x CPUs with firmware prior to v3.00 does not protect against additional software programming connections. An attacker can connect to the PLC while an existing connection is already active.Show less
1Automationdirect
20C0 10are D Firmware
C0 10dd1e D FirmwareC0 10dd2e D Firmware+17 more
Jun 17, 2026
Apr 4, 2022
N/A· v4
7.5 HIGH· v3
5.0 MEDIUM· v2
The programming protocol allows for a previously entered password and lock state to be read by an attacker. If the previously entered password was successful, the attacker can then use the password to unlock Automation D...Show more
The programming protocol allows for a previously entered password and lock state to be read by an attacker. If the previously entered password was successful, the attacker can then use the password to unlock Automation Direct CLICK PLC CPU Modules: C0-1x CPUs with firmware prior to v3.00.Show less
1Automationdirect
1C More Hmi Ea9 Firmware
Jun 17, 2026
Jul 23, 2020
N/A· v4
7.5 HIGH· v3
5.0 MEDIUM· v2
This vulnerability allows remote attackers to create a denial-of-service condition on affected installations of C-MORE HMI EA9 Firmware version 6.52 touch screen panels. Authentication is not required to exploit this vul...Show more
This vulnerability allows remote attackers to create a denial-of-service condition on affected installations of C-MORE HMI EA9 Firmware version 6.52 touch screen panels. Authentication is not required to exploit this vulnerability. The specific flaw exists within the EA-HTTP.exe process. The issue results from the lack of proper input validation prior to further processing user requests. An attacker can leverage this vulnerability to create a denial-of-service condition on the system. Was ZDI-CAN-10527.Show less
1Automationdirect
1C More Hmi Ea9 Firmware
Jun 17, 2026
Jul 23, 2020
N/A· v4
9.8 CRITICAL· v3
7.5 HIGH· v2
This vulnerability allows remote attackers to issue commands on affected installations of C-MORE HMI EA9 Firmware version 6.52 touch screen panels. Authentication is not required to exploit this vulnerability. The specif...Show more
This vulnerability allows remote attackers to issue commands on affected installations of C-MORE HMI EA9 Firmware version 6.52 touch screen panels. Authentication is not required to exploit this vulnerability. The specific flaw exists within the EA-HTTP.exe process. The issue results from the lack of authentication prior to allowing alterations to the system configuration. An attacker can leverage this vulnerability to issue commands to the physical equipment controlled by the device. Was ZDI-CAN-10482.Show less
1Automationdirect
1C More Hmi Ea9 Firmware
Jun 17, 2026
Jul 23, 2020
N/A· v4
9.8 CRITICAL· v3
7.5 HIGH· v2
This vulnerability allows remote attackers to execute arbitrary code on affected installations of C-MORE HMI EA9 Firmware version 6.52 touch screen panels. Authentication is not required to exploit this vulnerability. Th...Show more
This vulnerability allows remote attackers to execute arbitrary code on affected installations of C-MORE HMI EA9 Firmware version 6.52 touch screen panels. Authentication is not required to exploit this vulnerability. The specific flaw exists within the control service, which listens on TCP port 9999 by default. The issue results from the lack of authentication prior to allowing alterations to the system configuration. An attacker can leverage this vulnerability to execute code in the context of the device. Was ZDI-CAN-10493.Show less
1Automationdirect
1C More Hmi Ea9 Firmware
Jun 17, 2026
Jul 23, 2020
N/A· v4
5.9 MEDIUM· v3
4.3 MEDIUM· v2
This vulnerability allows remote attackers to disclose sensitive information on affected installations of C-MORE HMI EA9 Firmware version 6.52 touch screen panels. Authentication is not required to exploit this vulnerabi...Show more
This vulnerability allows remote attackers to disclose sensitive information on affected installations of C-MORE HMI EA9 Firmware version 6.52 touch screen panels. Authentication is not required to exploit this vulnerability. The specific flaw exists within the handling of passwords. When transmitting passwords, the process encrypts them in a recoverable format. An attacker can leverage this vulnerability to disclose credentials, leading to further compromise. Was ZDI-CAN-10185.Show less
1Automationdirect
1C More Hmi Ea9 Firmware
Jun 17, 2026
Jul 23, 2020
N/A· v4
7.5 HIGH· v3
5.0 MEDIUM· v2
This vulnerability allows remote attackers to bypass authentication on affected installations of C-MORE HMI EA9 Firmware version 6.52 touch screen panels. Authentication is not required to exploit this vulnerability. The...Show more
This vulnerability allows remote attackers to bypass authentication on affected installations of C-MORE HMI EA9 Firmware version 6.52 touch screen panels. Authentication is not required to exploit this vulnerability. The specific flaw exists within the authentication mechanism. The issue is due to insufficient authentication on post-authentication requests. An attacker can leverage this vulnerability to escalate privileges to resources normally protected from unauthenticated users. Was ZDI-CAN-10182.Show less
1Automationdirect
11C More Ea9 Rhi Firmware
C More Ea9 T10cl FirmwareC More Ea9 T10wcl Firmware+8 more
Jun 17, 2026
Feb 5, 2020
N/A· v4
9.8 CRITICAL· v3
10.0 HIGH· v2
It is possible to unmask credentials and other sensitive information on “unprotected” project files, which may allow an attacker to remotely access the C-More Touch Panels EA9 series: firmware versions prior to 6.53 and...Show more
It is possible to unmask credentials and other sensitive information on “unprotected” project files, which may allow an attacker to remotely access the C-More Touch Panels EA9 series: firmware versions prior to 6.53 and manipulate system configurations.Show less
1Automationdirect
5C More Micro Firmware
C More Plc FirmwareClick Plc Firmware+2 more
May 13, 2026
Nov 13, 2017
N/A· v4
7.8 HIGH· v3
9.3 HIGH· v2
In AutomationDirect CLICK Programming Software (Part Number C0-PGMSW) Versions 2.10 and prior; C-More Programming Software (Part Number EA9-PGMSW) Versions 6.30 and prior; C-More Micro (Part Number EA-PGMSW) Versions 4.2...Show more
In AutomationDirect CLICK Programming Software (Part Number C0-PGMSW) Versions 2.10 and prior; C-More Programming Software (Part Number EA9-PGMSW) Versions 6.30 and prior; C-More Micro (Part Number EA-PGMSW) Versions 4.20.01.0 and prior; Do-more Designer Software (Part Number DM-PGMSW) Versions 2.0.3 and prior; GS Drives Configuration Software (Part Number GSOFT) Versions 4.0.6 and prior; SL-SOFT SOLO Temperature Controller Configuration Software (Part Number SL-SOFT) Versions 1.1.0.5 and prior; and DirectSOFT Programming Software Versions 6.1 and prior, an uncontrolled search path element (DLL Hijacking) vulnerability has been identified. To exploit this vulnerability, an attacker could rename a malicious DLL to meet the criteria of the application, and the application would not verify that the DLL is correct. Once loaded by the application, the DLL could run malicious code at the privilege level of the application.Show less