← Back

Cp 8021 Master Module Firmware

cp-8021_master_module_firmware

Vendor: Siemens • 3 CVEs

CVEs (3)

CVE
VENDORS
PRODUCTS
UPDATED
PUBLISHED
CVSS
1Siemens
4Cp 8000 Master Module With I/o 25/+70 Firmware
Cp 8000 Master Module With I/o 40/+70 FirmwareCp 8021 Master Module Firmware+1 more
Oct 20, 2025
Aug 10, 2022
N/A· v4
7.5 HIGH· v3
N/A· v2
A vulnerability has been identified in CP-8000 MASTER MODULE WITH I/O -25/+70°C (All versions), CP-8000 MASTER MODULE WITH I/O -40/+70°C (All versions), CP-8021 MASTER MODULE (All versions), CP-8022 MASTER MODULE WITH GP...Show more
A vulnerability has been identified in CP-8000 MASTER MODULE WITH I/O -25/+70°C (All versions), CP-8000 MASTER MODULE WITH I/O -40/+70°C (All versions), CP-8021 MASTER MODULE (All versions), CP-8022 MASTER MODULE WITH GPRS (All versions). The component allows to activate a web server module which provides unauthenticated access to its web pages. This could allow an attacker to retrieve debug-level information from the component such as internal network topology or connected systems.Show less
1Siemens
4Cp 8000 Master Module With I/o 25/+70 Firmware
Cp 8000 Master Module With I/o 40/+70 FirmwareCp 8021 Master Module Firmware+1 more
Nov 21, 2024
Jan 11, 2022
N/A· v4
7.5 HIGH· v3
4.3 MEDIUM· v2
A vulnerability has been identified in CP-8000 MASTER MODULE WITH I/O -25/+70°C (All versions < V16.20), CP-8000 MASTER MODULE WITH I/O -40/+70°C (All versions < V16.20), CP-8021 MASTER MODULE (All versions < V16.20), CP...Show more
A vulnerability has been identified in CP-8000 MASTER MODULE WITH I/O -25/+70°C (All versions < V16.20), CP-8000 MASTER MODULE WITH I/O -40/+70°C (All versions < V16.20), CP-8021 MASTER MODULE (All versions < V16.20), CP-8022 MASTER MODULE WITH GPRS (All versions < V16.20). The web server of the affected system allows access to logfiles and diagnostic data generated by a privileged user. An unauthenticated attacker could access the files by knowing the corresponding download links.Show less
1Siemens
4Cp 8000 Master Module With I/o 25/+70 Firmware
Cp 8000 Master Module With I/o 40/+70 FirmwareCp 8021 Master Module Firmware+1 more
Nov 21, 2024
Jan 11, 2022
N/A· v4
8.8 HIGH· v3
8.5 HIGH· v2
A vulnerability has been identified in CP-8000 MASTER MODULE WITH I/O -25/+70°C (All versions < V16.20), CP-8000 MASTER MODULE WITH I/O -40/+70°C (All versions < V16.20), CP-8021 MASTER MODULE (All versions < V16.20), CP...Show more
A vulnerability has been identified in CP-8000 MASTER MODULE WITH I/O -25/+70°C (All versions < V16.20), CP-8000 MASTER MODULE WITH I/O -40/+70°C (All versions < V16.20), CP-8021 MASTER MODULE (All versions < V16.20), CP-8022 MASTER MODULE WITH GPRS (All versions < V16.20). An undocumented debug port uses hard-coded default credentials. If this port is enabled by a privileged user, an attacker aware of the credentials could access an administrative debug shell on the affected device.Show less