1Rockwellautomation
171756 Enbt
1756 Eweb1768 Enbt+14 more
Apr 29, 2026
Jan 24, 2013
N/A· v4
N/A· v3
5.0 MEDIUM· v2
An information exposure of confidential information results when the device receives a specially crafted CIP packet to Port 2222/TCP, Port 2222/UDP, Port 44818/TCP, or Port 44818/UDP. Successful exploitation of this vuln...Show more
An information exposure of confidential information results when the device receives a specially crafted CIP packet to Port 2222/TCP, Port 2222/UDP, Port 44818/TCP, or Port 44818/UDP. Successful exploitation of this vulnerability could cause loss of confidentiality. Rockwell Automation EtherNet/IP products; 1756-ENBT, 1756-EWEB, 1768-ENBT, and 1768-EWEB communication modules; CompactLogix L32E and L35E controllers; 1788-ENBT FLEXLogix adapter; 1794-AENTR FLEX I/O EtherNet/IP adapter; ControlLogix 18 and earlier; CompactLogix 18 and earlier; GuardLogix 18 and earlier; SoftLogix 18 and earlier; CompactLogix controllers 19 and earlier; SoftLogix controllers 19 and earlier; ControlLogix controllers 20 and earlier; GuardLogix controllers 20 and earlier; and MicroLogix 1100 and 1400Show less
1Rockwellautomation
171756 Enbt
1756 Eweb1768 Enbt+14 more
Jun 3, 2026
Jan 24, 2013
N/A· v4
4.8 MEDIUM· v3
9.3 HIGH· v2
The Web server password authentication mechanism used by the products is vulnerable to a MitM and Replay attack. Successful exploitation of this vulnerability will allow unauthorized access of the product’s Web server to...Show more
The Web server password authentication mechanism used by the products is vulnerable to a MitM and Replay attack. Successful exploitation of this vulnerability will allow unauthorized access of the product’s Web server to view and alter product configuration and diagnostics information. Rockwell Automation EtherNet/IP products; 1756-ENBT, 1756-EWEB, 1768-ENBT, and 1768-EWEB communication modules; CompactLogix L32E and L35E controllers; 1788-ENBT FLEXLogix adapter; 1794-AENTR FLEX I/O EtherNet/IP adapter; ControlLogix 18 and earlier; CompactLogix 18 and earlier; GuardLogix 18 and earlier; SoftLogix 18 and earlier; CompactLogix controllers 19 and earlier; SoftLogix controllers 19 and earlier; ControlLogix controllers 20 and earlier; GuardLogix controllers 20 and earlier; and MicroLogix 1100 and 1400Show less
1Rockwellautomation
171756 Enbt
1756 Eweb1768 Enbt+14 more
Apr 29, 2026
Jan 24, 2013
N/A· v4
N/A· v3
8.5 HIGH· v2
When an affected product receives a valid CIP message from an unauthorized or unintended source to Port 2222/TCP, Port 2222/UDP, Port 44818/TCP, or Port 44818/UDP that changes the product’s configuration and network...Show more
When an affected product receives a valid CIP message from an unauthorized or unintended source to Port 2222/TCP, Port 2222/UDP, Port 44818/TCP, or Port 44818/UDP that changes the product’s configuration and network parameters, a DoS condition can occur. This situation could cause loss of availability and a disruption of communication with other connected devices.  Rockwell Automation EtherNet/IP products; 1756-ENBT, 1756-EWEB, 1768-ENBT, and 1768-EWEB communication modules; CompactLogix L32E and L35E controllers; 1788-ENBT FLEXLogix adapter; 1794-AENTR FLEX I/O EtherNet/IP adapter; ControlLogix 18 and earlier; CompactLogix 18 and earlier; GuardLogix 18 and earlier; SoftLogix 18 and earlier; CompactLogix controllers 19 and earlier; SoftLogix controllers 19 and earlier; ControlLogix controllers 20 and earlier; GuardLogix controllers 20 and earlier; and MicroLogix 1100 and 1400Show less
1Rockwellautomation
171756 Enbt
1756 Eweb1768 Enbt+14 more
Jun 3, 2026
Jan 24, 2013
N/A· v4
7.5 HIGH· v3
7.8 HIGH· v2
The device does not properly validate the data being sent to the buffer. An attacker can send a malformed CIP packet to Port 2222/TCP, Port 2222/UDP, Port 44818/TCP, or Port 44818/UDP, which creates a buffer overflow and...Show more
The device does not properly validate the data being sent to the buffer. An attacker can send a malformed CIP packet to Port 2222/TCP, Port 2222/UDP, Port 44818/TCP, or Port 44818/UDP, which creates a buffer overflow and causes the NIC to crash. Successful exploitation of this vulnerability could cause loss of availability and a disruption in communications with other connected devices. Rockwell Automation EtherNet/IP products; 1756-ENBT, 1756-EWEB, 1768-ENBT, and 1768-EWEB communication modules; CompactLogix L32E and L35E controllers; 1788-ENBT FLEXLogix adapter; 1794-AENTR FLEX I/O EtherNet/IP adapter; ControlLogix 18 and earlier; CompactLogix 18 and earlier; GuardLogix 18 and earlier; SoftLogix 18 and earlier; CompactLogix controllers 19 and earlier; SoftLogix controllers 19 and earlier; ControlLogix controllers 20 and earlier; GuardLogix controllers 20 and earlier; and MicroLogix 1100 and 1400Show less
1Rockwellautomation
171756 Enbt
1756 Eweb1768 Enbt+14 more
Jun 3, 2026
Jan 24, 2013
N/A· v4
9.8 CRITICAL· v3
10.0 HIGH· v2
The device does not properly authenticate users and the potential exists for a remote user to upload a new firmware image to the Ethernet card, whether it is a corrupt or legitimate firmware image. Successful exploitatio...Show more
The device does not properly authenticate users and the potential exists for a remote user to upload a new firmware image to the Ethernet card, whether it is a corrupt or legitimate firmware image. Successful exploitation of this vulnerability could cause loss of availability, integrity, and confidentiality and a disruption in communications with other connected devices. Rockwell Automation EtherNet/IP products; 1756-ENBT, 1756-EWEB, 1768-ENBT, and 1768-EWEB communication modules; CompactLogix L32E and L35E controllers; 1788-ENBT FLEXLogix adapter; 1794-AENTR FLEX I/O EtherNet/IP adapter; ControlLogix 18 and earlier; CompactLogix 18 and earlier; GuardLogix 18 and earlier; SoftLogix 18 and earlier; CompactLogix controllers 19 and earlier; SoftLogix controllers 19 and earlier; ControlLogix controllers 20 and earlier; GuardLogix controllers 20 and earlier; and MicroLogix 1100 and 1400Show less
1Rockwellautomation
171756 Enbt
1756 Eweb1768 Enbt+14 more
Jun 3, 2026
Jan 24, 2013
N/A· v4
7.5 HIGH· v3
7.8 HIGH· v2
The device does not properly validate the data being sent to the buffer. An attacker can send a malformed CIP packet to Port 2222/TCP, Port 2222/UDP, Port 44818/TCP, or Port 44818/UDP, which creates a buffer overflow and...Show more
The device does not properly validate the data being sent to the buffer. An attacker can send a malformed CIP packet to Port 2222/TCP, Port 2222/UDP, Port 44818/TCP, or Port 44818/UDP, which creates a buffer overflow and causes the CPU to crash. Successful exploitation of this vulnerability could cause loss of availability and a disruption in communications with other connected devices. Rockwell Automation EtherNet/IP products; 1756-ENBT, 1756-EWEB, 1768-ENBT, and 1768-EWEB communication modules; CompactLogix L32E and L35E controllers; 1788-ENBT FLEXLogix adapter; 1794-AENTR FLEX I/O EtherNet/IP adapter; ControlLogix 18 and earlier; CompactLogix 18 and earlier; GuardLogix 18 and earlier; SoftLogix 18 and earlier; CompactLogix controllers 19 and earlier; SoftLogix controllers 19 and earlier; ControlLogix controllers 20 and earlier; GuardLogix controllers 20 and earlier; and MicroLogix 1100 and 1400Show less
1Rockwellautomation
171756 Enbt
1756 Eweb1768 Enbt+14 more
Jun 3, 2026
Jan 24, 2013
N/A· v4
7.5 HIGH· v3
7.8 HIGH· v2
When an affected product receives a valid CIP message from an unauthorized or unintended source to Port 2222/TCP, Port 2222/UDP, Port 44818/TCP, or Port 44818/UDP that instructs the CPU to stop logic execution and enter...Show more
When an affected product receives a valid CIP message from an unauthorized or unintended source to Port 2222/TCP, Port 2222/UDP, Port 44818/TCP, or Port 44818/UDP that instructs the CPU to stop logic execution and enter a fault state, a DoS can occur. This situation could cause loss of availability and a disruption of communication with other connected devices. Rockwell Automation EtherNet/IP products; 1756-ENBT, 1756-EWEB, 1768-ENBT, and 1768-EWEB communication modules; CompactLogix L32E and L35E controllers; 1788-ENBT FLEXLogix adapter; 1794-AENTR FLEX I/O EtherNet/IP adapter; ControlLogix 18 and earlier; CompactLogix 18 and earlier; GuardLogix 18 and earlier; SoftLogix 18 and earlier; CompactLogix controllers 19 and earlier; SoftLogix controllers 19 and earlier; ControlLogix controllers 20 and earlier; GuardLogix controllers 20 and earlier; and MicroLogix 1100 and 1400Show less