CVE-2023-50233
8.8
Vector
CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H
Exploitability: 2.8 / Impact: 5.9
Source: NVD
Description
Inductive Automation Ignition getJavaExecutable Directory Traversal Remote Code Execution Vulnerability. This vulnerability allows remote attackers to execute arbitrary code on affected installations of Inductive Automation Ignition. User interaction is required to exploit this vulnerability in that the target must connect to a malicious server.
The specific flaw exists within the getJavaExecutable method. The issue results from the lack of proper validation of a user-supplied path prior to using it in file operations. An attacker can leverage this vulnerability to execute code in the context of the current user. Was ZDI-CAN-22029.
Affected (1)
Products: Inductiveautomation: Ignition
Configuration A
| Vulnerable Software | Affected Versions |
|---|---|
| From 8.1.0 to 8.1.33 |
References (4)
Source: zdi-disclosures@trendmicro.com
Vendor Advisory
Source: zdi-disclosures@trendmicro.com
Third Party Advisory
Source: af854a3a-2127-422b-91ae-364da2661108
Vendor Advisory
Source: af854a3a-2127-422b-91ae-364da2661108
Third Party Advisory
Timeline
No history available yet.