CVE-2023-2071
9.8
Vector
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
Exploitability: 3.9 / Impact: 5.9
Source: NVD
Description
Rockwell Automation FactoryTalk View Machine Edition on the PanelView Plus, improperly verifies user’s input, which allows unauthenticated attacker to achieve remote code executed via crafted malicious packets. The device has the functionality, through a CIP class, to execute exported functions from libraries. There is a routine that restricts it to execute specific functions from two dynamic link library files. By using a CIP class, an attacker can upload a self-made library to the device which allows the attacker to bypass the security check and execute any code written in the function.
Affected (1)
Products: Rockwellautomation: Factorytalk View
Configuration A
| Vulnerable Software | Affected Versions |
|---|---|
| Up to 13.0 |
| Running on/with | Platform Versions |
|---|---|
Rockwellautomation Panelview Plus | All versions |
Related CWEs
CWE-20
Improper Input Validation
The product receives input or data, but it does
not validate or incorrectly validates that the input has the
properties that are required to process the data safely and
correctly.
CWE-434
Unrestricted Upload of File with Dangerous Type
The product allows the upload or transfer of dangerous file types that are automatically processed within its environment.
References (2)
Source: PSIRT@rockwellautomation.com
Vendor Advisory
Source: af854a3a-2127-422b-91ae-364da2661108
Vendor Advisory
Timeline