CVE-2022-4608
7.5
Vector
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
Exploitability: 3.9 / Impact: 3.6
Source: NVD
Description
A vulnerability exists in HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-3. After session resumption interval is expired an RTU500 initiated update of session parameters causes an unexpected restart due to a stack overflow.
Affected (4)
Products: Hitachienergy: Rtu500 Firmware
Configuration A
| Vulnerable Software | Affected Versions |
|---|---|
| Version 13.3.1 |
| Running on/with | Platform Versions |
|---|---|
Hitachienergy Rtu500 | All versions |
References (2)
Source: cybersecurity@hitachienergy.com
Source: af854a3a-2127-422b-91ae-364da2661108
Timeline
No history available yet.