Description

Saia Burgess Controls (SBC) PCD through 2022-05-06 uses a Broken or Risky Cryptographic Algorithm. According to FSCT-2022-0063, there is a Saia Burgess Controls (SBC) PCD S-Bus weak credential hashing scheme issue. The affected components are characterized as: S-Bus (5050/UDP) authentication. The potential impact is: Authentication bypass. The Saia Burgess Controls (SBC) PCD controllers utilize the S-Bus protocol (5050/UDP) for a variety of engineering purposes. It is possible to configure a password in order to restrict access to sensitive engineering functionality. Authentication is done by using the S-Bus 'write byte' message to a specific address and supplying a hashed version of the password. The hashing algorithm used is based on CRC-16 and as such not cryptographically secure. An insecure hashing algorithm is used. An attacker capable of passively observing traffic can intercept the hashed credentials and trivially find collisions allowing for authentication without having to bruteforce a keyspace defined by the actual strength of the password. This allows the attacker access to sensitive engineering functionality such as uploading/downloading control logic and manipulating controller configuration.

Affected (1)

1 product
Saia Pg5 Controls Suite
Configuration A
1 vulnerable
Vulnerable SoftwareAffected Versions
All versions

References (4)

Source: cve@mitre.org
Third Party AdvisoryUS Government Resource
Source: cve@mitre.org
Not ApplicableThird Party Advisory
Source: af854a3a-2127-422b-91ae-364da2661108
Third Party AdvisoryUS Government Resource
Source: af854a3a-2127-422b-91ae-364da2661108
Not ApplicableThird Party Advisory

Timeline

No history available yet.