Description
A vulnerability exists in the HCI Modbus TCP function included in the product versions listed above. If the HCI Modbus TCP is en-abled and configured, an attacker could exploit the vulnerability by sending a specially crafted message to the RTU500, causing the receiving RTU500 CMU to reboot. The vulnerability is caused by the validation error in the length information carried in MBAP header in the HCI Modbus TCP function.
Affected (6)
Products: Abb: Rtu500 Firmware · Hitachienergy: Rtu500 Firmware
Configuration A
| Vulnerable Software | Affected Versions |
|---|---|
| From 12.2.1.0 to 12.2.12.0 | |
| From 12.0.1.0 to 12.0.14.0 |
| Running on/with | Platform Versions |
|---|---|
Hitachienergy Rtu500 | All versions |
References (2)
Source: cybersecurity@hitachienergy.com
Source: af854a3a-2127-422b-91ae-364da2661108
Timeline
No history available yet.