CVE-2021-40360
8.8
Vector
CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H
Exploitability: 2.8 / Impact: 5.9
Source: NVD
Description
A vulnerability has been identified in SIMATIC PCS 7 V8.2 (All versions), SIMATIC PCS 7 V9.0 (All versions), SIMATIC PCS 7 V9.1 (All versions < V9.1 SP1), SIMATIC WinCC V15 and earlier (All versions < V15 SP1 Update 7), SIMATIC WinCC V16 (All versions < V16 Update 5), SIMATIC WinCC V17 (All versions < V17 Update 2), SIMATIC WinCC V7.4 (All versions < V7.4 SP1 Update 19), SIMATIC WinCC V7.5 (All versions < V7.5 SP2 Update 6). The password hash of a local user account in the remote server could be granted via public API to a user on the affected system. An authenticated attacker could brute force the password hash and use it to login to the server.
Affected (53)
Products: Siemens: Simatic Pcs 7, Simatic Wincc
Configuration A
| Vulnerable Software | Affected Versions |
|---|---|
| Up to 8.2 | |
| Before 7.4 |
Related CWEs
CWE-200
Exposure of Sensitive Information to an Unauthorized Actor
The product exposes sensitive information to an actor that is not explicitly authorized to have access to that information.
CWE-522
Insufficiently Protected Credentials
The product transmits or stores authentication credentials, but it uses an insecure method that is susceptible to unauthorized interception and/or retrieval.
References (2)
Source: productcert@siemens.com
PatchVendor Advisory
Source: af854a3a-2127-422b-91ae-364da2661108
PatchVendor Advisory
Timeline