CVE-2019-19279
7.5
Vector
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
Exploitability: 3.9 / Impact: 3.6
Source: NVD
Description
A vulnerability has been identified in SIPROTEC 4 and SIPROTEC Compact relays equipped with EN100 Ethernet communication modules (All versions). Specially crafted packets sent to port 50000/UDP of the EN100 Ethernet communication modules could cause a Denial-of-Service of the affected device. A manual reboot is required to recover the service of the device. At the time of advisory publication no public exploitation of this security vulnerability was known to Siemens.
Affected (2)
Products: Siemens: Siprotec 4, Siprotec Compact
Configuration A
| Vulnerable Software | Affected Versions |
|---|---|
| All versions | |
| All versions |
References (2)
Source: productcert@siemens.com
Vendor Advisory
Source: af854a3a-2127-422b-91ae-364da2661108
Vendor Advisory
Timeline
No history available yet.