← Back

CVE-2019-10935

nvd nist
Published: Jul 11, 2019Modified: Nov 21, 2024

JSON object

Loading...
7.2
Vector
CVSS:3.0/AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H
Exploitability: 1.2 / Impact: 5.9
Source: NVD

Description

A vulnerability has been identified in SIMATIC PCS 7 V8.0 and earlier (All versions), SIMATIC PCS 7 V8.1 (All versions < V8.1 with WinCC V7.3 Upd 19), SIMATIC PCS 7 V8.2 (All versions < V8.2 SP1 with WinCC V7.4 SP1 Upd 11), SIMATIC PCS 7 V9.0 (All versions < V9.0 SP2 with WinCC V7.4 SP1 Upd11), SIMATIC WinCC Professional (TIA Portal V13) (All versions), SIMATIC WinCC Professional (TIA Portal V14) (All versions < V14 SP1 Upd 9), SIMATIC WinCC Professional (TIA Portal V15) (All versions < V15.1 Upd 3), SIMATIC WinCC Runtime Professional V13 (All versions), SIMATIC WinCC Runtime Professional V14 (All versions < V14.1 Upd 8), SIMATIC WinCC Runtime Professional V15 (All versions < V15.1 Upd 3), SIMATIC WinCC V7.2 and earlier (All versions), SIMATIC WinCC V7.3 (All versions < V7.3 Upd 19), SIMATIC WinCC V7.4 (All versions < V7.4 SP1 Upd 11), SIMATIC WinCC V7.5 (All versions < V7.5 Upd 3). The SIMATIC WinCC DataMonitor web application of the affected products allows to upload arbitrary ASPX code. The security vulnerability could be exploited by an authenticated attacker with network access to the WinCC DataMonitor application. No user interaction is required to exploit this vulnerability. The vulnerability impacts confidentiality, integrity, and availability of the affected device. At the stage of publishing this security advisory no public exploitation is known.

Affected (32)

3 products
Simatic Pcs 7
Simatic Wincc
Simatic Wincc Runtime
Configuration A
4 vulnerable
Vulnerable SoftwareAffected Versions
Siemens
Version 8.0
Version 8.1
Version 8.2
Version 9.0
Configuration B
11 vulnerable
Vulnerable SoftwareAffected Versions
Siemens
Up to 7.2
Version 7.3
Version 7.3 update_10
Version 7.3 update_11
Version 7.3 update_13
Version 7.3 update_1
Version 7.3 update_4
Version 7.4
Version 7.4 sp1
Version 7.4 update_1
Version 7.5
Configuration C
6 vulnerable
Vulnerable SoftwareAffected Versions
Siemens
Version 13
Version 13 sp2
Version 14
Version 14
Version 14 sp1
Version 15
Configuration D
11 vulnerable

References (2)

Source: productcert@siemens.com
PatchVendor Advisory
Source: af854a3a-2127-422b-91ae-364da2661108
PatchVendor Advisory

Timeline

No history available yet.