nvd nist
Published: Dec 13, 2018Modified: Nov 21, 2024

JSON object

Loading...
7.5
Vector
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
Exploitability: 3.9 / Impact: 3.6
Source: productcert@siemens.com (Secondary)

Description

A vulnerability has been identified in SIMATIC S7-400 CPU 412-1 DP V7 (All versions), SIMATIC S7-400 CPU 412-2 DP V7 (All versions), SIMATIC S7-400 CPU 414-2 DP V7 (All versions), SIMATIC S7-400 CPU 414-3 DP V7 (All versions), SIMATIC S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 414F-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 416-2 DP V7 (All versions), SIMATIC S7-400 CPU 416-3 DP V7 (All versions), SIMATIC S7-400 CPU 416-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 416F-2 DP V7 (All versions), SIMATIC S7-400 CPU 416F-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 417-4 DP V7 (All versions), SIMATIC S7-400 CPU 412-2 PN V7 (All versions < V7.0.3), SIMATIC S7-400 H V4.5 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 H V6 CPU family (incl. SIPLUS variants) (All versions < V6.0.9), SIMATIC S7-400 PN/DP V6 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-410 CPU family (incl. SIPLUS variants) (All versions < V8.2.1), SIPLUS S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3), SIPLUS S7-400 CPU 416-3 PN/DP V7 (All versions < V7.0.3), SIPLUS S7-400 CPU 416-3 V7 (All versions), SIPLUS S7-400 CPU 417-4 V7 (All versions). Specially crafted packets sent to port 102/tcp via Ethernet interface, via PROFIBUS, or via Multi Point Interfaces (MPI) could cause the affected devices to go into defect mode. Manual reboot is required to resume normal operation. Successful exploitation requires an attacker to be able to send specially crafted packets to port 102/tcp via Ethernet interface, via PROFIBUS or Multi Point Interfaces (MPI). No user interaction and no user privileges are required to exploit the security vulnerability. The vulnerability could allow causing a denial of service condition of the core functionality of the CPU, compromising the availability of the system.

Affected (5)

5 products
Simatic S7 400 Firmware
Simatic S7 400 Pn/dp V7 Firmware
Simatic S7 400h Firmware
Simatic S7 410 Firmware
Simatic S7 400h V6 Firmware
Configuration A
1 vulnerable · 1 platform
Vulnerable SoftwareAffected Versions
Up to v6.0
Running on/withPlatform Versions
Siemens
Simatic S7 400
All versions
Configuration B
1 vulnerable · 1 platform
Vulnerable SoftwareAffected Versions
All versions
Running on/withPlatform Versions
Siemens
Simatic S7 400 Pn/dp V7
All versions
Configuration C
1 vulnerable · 1 platform
Vulnerable SoftwareAffected Versions
Up to v4.5
Running on/withPlatform Versions
Siemens
Simatic S7 400h
All versions
Configuration D
1 vulnerable · 1 platform
Vulnerable SoftwareAffected Versions
Before 8.2.1
Running on/withPlatform Versions
Siemens
Simatic S7 410
All versions
Configuration E
1 vulnerable · 1 platform
Vulnerable SoftwareAffected Versions
All versions
Running on/withPlatform Versions
Siemens
Simatic S7 400h V6
All versions

References (2)

Source: productcert@siemens.com
Vendor Advisory
Source: af854a3a-2127-422b-91ae-364da2661108
Vendor Advisory

Timeline